IR Alarm. This indicator turns on when the IR alarm criteria are met.

Unable to Configure. This bit is set by the gateway when it was
unable to successfully transfer configuration information to the UV/IR
flame detector.

Inhibit Active. This bit turns on to indicate that the gateway relays
and display are inhibited from responding to changes in the UV/IR
flame detector status. The inhibit active status bit is controlled by the
“Inhibit” button.

Not Communicating. This bit is set by the gateway when its diag-
nostic routine indicates that it has not received periodic status messages
from the flame detector. The bit is cleared when a new status update is
received.

UV Alarm. This indicator turns on when the UV alarm criteria are met.

Invalid Configuration. This bit indicates that configuration informa-
tion is invalid and is set on a new unit, when the address is changed,
or when invalid data is transferred. A valid configuration must be down-
loaded to clear the bit.

UV Fault. This bit is set when a fault relating to the UV sensor is detect-
ed. Press the extended status button to locate the source of the problem.

IR Fault. This bit is set when a fault relating to the IR sensor is detect-
ed. Press the extended status button to locate the source of the problem.

Power-Up. This indicator is on while the detector is conducting self-
diagnostics after re-application of power.

Auto Configuration Fault. This bit indicates that the gateway was
unable to successfully download configuration information.

Fault. This bit is set for all fault conditions and tracks the fire trouble
signal sent to the logic controller.

Fire Alarm. This bit tracks the fire alarm signal sent to the logic con-
troller, and turns on when both the UV and IR fire alarm criteria are met.

U

PDATE

R

ATE

This field shows in milliseconds how often the UV/IR detector will report
its status to the gateway. The update rate is programmable from 1 to 10
seconds on the UV/IR detector configuration screen.