Det-Tronics EagleVision - PC User Manual

Page 74

Advertising
background image

U

PDATE

R

ATE

This field shows in milliseconds how often the detector will report its sta-
tus to the gateway. The update rate is programmable from 1 to 10 sec-
onds on the UV detector configuration screen.

S

ENSITIVITY

, T

IME

D

ELAY

,

AND

A

RC

R

EJECTION

This area displays the fire response configuration parameters. These
parameters are programmable from the UV detector configuration
screen.

D

ETECTOR

M

ODE

Processing mode. This field indicates whether the detector is config-
ured for standard or arc rejection signal processing mode.

Oi. This field shows if the detector is configured for automatic optical
integrity testing. Manual Oi testing is always available.

Latching. This field indicates whether the detector’s alarm output is
configured for latching or non-latching operation. If latching mode is
selected, the detector can be reset with the Reset button.

A

LARM

A

DDRESSES

This area lists the addresses of the logic controllers that are configured
for communication with this UV detector. All alarm and trouble status
signals will be sent to the addresses listed here. The addresses can be
changed on the UV detector configuration screen.

A

LARM

H

ISTORY

The UV detector stores the time and date of the last eight fire alarms.
This information is displayed by pressing the Fetch Logs button.

B

UTTONS

Reset. This button resets the alarm condition when latching operation
is selected.

Start Oi Test. This button initiates a manual Oi test. The test will run
for a pre-determined length of time and will end automatically. If the
detector fails the test, the manual Oi fault bit is set.

Fetch Logs Button. This button will retrieve the alarm logs.

95-8479

7.17

E

AGLE

Q

UANTUM

P

OINT

D

ISPLAYS