NV Communicating. This bit is set when a field device is not report-
ing to the logic controller. The Detect NV Comm button can be used to
identify any devices that are not reporting.

Detect NV Comm. This feature is used to identify field devices that
are not reporting to the logic controller. A listing of all field devices and
their current communication status will be provided in the box in the
lower left hand corner of the screen.

L

OGIC

C

ONTROLLER

S

TATUS

Fire Alarm. This bit tracks the Alarm LED on the logic controller face-
plate. The fire alarm status bit is activated when any enabled fire input
is active. This includes all flame detectors and IDC inputs that are con-
figured as alarm type inputs. The bit is latching and will remain active
until the logic controller is reset.

Trouble. This bit tracks the Trouble LED on the logic controller face-
plate. Once the trouble bit is set, it can only be cleared by resetting the
logic controller. The trouble bit is set when any of the following faults
are active:

• LIOU Not Communicating
• AC Failed
• Battery Fault
• LIOU Wire Fault
• Power Supply Fault
• Power Trouble
• LIOU Too Many Cards
• Invalid Configuration
• Upper Xcvr Fault
• Lower Xcvr Fault
• LON Fault
• NV Input Not Communicating
• GW LON Fault
• RAM Fault.

Supervisory. This bit tracks the Supervisory LED on the logic controller
faceplate. The supervisory status bit is set when any enabled LON input
has a supervisory fault. The bit is latching and remains set until the logic
controller is reset.

Acknowledge. The acknowledge status bit is set after the acknowl-
edge switch on the logic controller faceplate is activated. It indicates
that the operator has acknowledged an alarm condition and silenced
the internal beeper. The bit is latching and will remain set until the logic
controller is reset.