Det-Tronics EagleVision - PC User Manual

Page 38

Advertising
background image

D

OWNLOAD

RTC

Select “Download RTC” to download the Real Time Clock (RTC) value
from the computer to the selected gateway. This synchronizes the gate-
way clock to the OIS clock.

U

PLOAD

RTC

Select “Upload RTC” to upload the Real Time Clock (RTC) value from the
selected gateway. This allows the operator to view the gateway
date/time clock values without affecting the computer’s clock.

W

RITE

EEPROM

(E

LECTRONICALLY

E

RASABLE

P

ROGRAMMABLE

R

EAD

O

NLY

M

EMORY

)

After downloading the configuration data, highlight the appropriate
Gateway or Logic Controller address and click on Write EEPROM to
write the data to non-volatile memory. This ensures that the data will not
be lost in the event of a power loss.

NOTE

Logic controllers must be placed in Reset/Program mode while
downloading data.

To obtain a permanent record of system configuration data, from the
Point Configuration screen select Print under the File menu. EagleVision-
NT will print a list of configuration data for each point in the system.
Note that while the data contained in the printout exactly matches the
data on the point configuration screen for the device, the two formats
will be different. Printed information includes the following.

For gateways, printed data includes device type and trigger, starting
and ending addresses of monitored nodes for each gateway relay,
Modbus address, master data offset and AB file number. The event trig-
gers that can be selected for activation of each of the gateway relays
are represented by the numbers 1 to 16 (these numbers correspond to
the gateway status bits). An “X” next to a number indicates that the sta-
tus condition has been selected. Refer to the Gateway Configuration
screen (Figure V-3) for identification of the status bits.

For logic controllers, printed data includes device type and trigger as
well as type and address of LIOU devices with configuration data
unique to each device.

For LON devices, printed data includes device type, trigger, update
rate, destination address, as well as any other configuration data
applicable to the device type.

5.22

E

AGLE

Q

UANTUM

S

YSTEM

C

ONFIGURATION

P

RINTING

C

ONFIGURATION

D

ATA

Advertising