IO Communication Fault. This bit signals a general fault with the
RS-485 communication with the EQ2100LIOU boards or
EQ2100LCUPS power supply.

IO Board Count. This bit is set when an EQ2100LIOU board is
detected that is not on the list of configured boards. Use the “Detect
Cards” feature to locate the problem (accessed by pressing the
Diagnostic button).

IO Wire Fault. This fault bit is set when any of the EQ2100LIOU
boards have an open or shorted wire. Check the individual card status
to locate the cause of the problem.

IO CPU Reset. This fault bit is set when any of the EQ2100LIOU
boards has been reset. Check the card status to locate the card that has
been reset.

IO Not Communicating. This bit is set when one or more of the con-
figured IO boards is not responding. Check the card status to locate the
card that is not responding.

LIOU C

ARD

S

TATUS

When the Card Status button is pressed, a tabbed notebook is dis-
played on the lower part of the screen. The tabs are numbered 1 to 24
to represent the maximum number of LIOU boards and LCUPS power
supplies. Each page of the notebook displays the current status of the
device installed at that location. The last tab is labeled LH (local hard-
ware).

Sounder Board

See Figure VII–3. The Sounder board has open and shorted fault con-
dition indicators for each of the 4 supervised output circuits.

CPU Reset — status is activated for 60 seconds when a board is reset
from power-up, by the watchdog timer, or by pressing the reset switch
on the board.

Wrong Style Cir — activated when the software configuration does
not match the DIP switch setting on the board.

Not Communicating — board is not responding.

95-8479

7.7

E

AGLE

Q

UANTUM

P

OINT

D

ISPLAYS