UV/IR Sensitivity. This field shows the sensitivity settings for the UV
and IR sensors. The UV setting is on the left, while the IR sensitivity is on
the right. The sensitivity settings can be adjusted from the UV/IR detec-
tor configuration screen.

Arc Rejection. This field indicates whether the UV sensor is configured
for standard or arc rejection signal processing mode.

Time Delay. This field shows the selected alarm time delay. The fire
must be present for this amount of time to be considered an alarm. The
time delay can be adjusted from the UV/IR configuration screen.

IR Oi Sensitivity. This field shows the selected Oi sensitivity setting for
the IR sensor. When low sensitivity is selected, the IR sensor will fault
with less contamination on the viewing window than when medium or
high sensitivity is selected. The IR Oi sensitivity setting can be adjusted
from the UV/IR detector configuration screen.

Processing Mode. This field indicates whether the UV sensor is con-
figured for standard or arc rejection signal processing mode. This can
be adjusted from the UV/IR detector configuration screen.

Oi. This field indicates if the detector is configured for automatic opti-
cal testing. Manual Oi testing is always available.

Oi Test Frequency. This field shows how often the IR sensor will be
automatically tested. The setting can be changed on the UV/IR detector
configuration screen.

Latching. This field indicates whether the detector’s alarm output sig-
nal is configured for latching or non-latching operation. If latching mode
is selected, the unit can be reset with the reset button.

Alarm Destination Addresses. This area shows the addresses of
the logic controllers that are configured for communication with this
UV/IR detector. All alarm and trouble status signals will be sent to the
addresses listed here. The addresses can be changed on the UV/IR
detector configuration screen.

A

LARM

H

ISTORY

The detector stores the time and date of the last eight fire alarms. This
information is displayed by pressing the Fetch Logs button.