From the Point Configuration screen, highlight the UV/IR Flame
Detector, then click on Display Point or select Point from the View menu.
The UV/IR Flame Detector Point Display screen will be displayed. See
Figure VII–11.

B

AR

G

RAPH

D

ISPLAY

The bar graph display shows the current UV or IR signal in counts per
second (cps). The “Display IR / UV” button allows the operator to switch
between the two channels. Two scales are displayed for each channel
— a 1x (times 1) and a 10x (times 10). In normal operation, the UV sig-
nal should be zero and the IR signal should be a low level between 5
and 15 cps. When an automatic Oi (optical integrity) test is in progress,
a small signal level is visible. A small signal is also visible when a man-
ual Oi test is performed, or when a background UV or IR source is
detected.

S

TATUS

I

NDICATORS

Low Voltage. This indicator turns on when the input power voltage to
the detector is below 17.5 volts.

Com 1 / Com 2. One of these bits is set when the fault isolation cir-
cuitry in the detector has detected and isolated a LON wiring fault.

7.18

E

AGLE

Q

UANTUM

P

OINT

D

ISPLAYS

UV/IR F

LAME

D

ETECTOR

P

OINT

D

ISPLAY

SETTINGS DISPLAY

FIGURE VII-11

UV/IR Flame Detector
Point Display Screen