Upper or Lower Xcever Fault. These bits indicate that the self-diag-
nostic tests have detected a malfunction in one of the two LON commu-
nication transceivers.

LON Fault. This bit is set when the logic controller is not receiving
heartbeats from the main gateway.

Unable to Configure. This bit indicates that the main gateway was
unable to successfully transfer configuration information to the logic con-
troller.

Invalid Configuration. The invalid configuration status is active until
configuration information is downloaded. Changing the logic controller
address will cause the invalid configuration status to indicate that recon-
figuration is required.

Not Communicating. This bit is set when the logic controller fails to
report on schedule.

EEPROM CRC. Using a cyclical redundancy check method, the auto-
matic self-diagnostic test has revealed a problem with the non-volatile
memory. The logic controller must be replaced if this error occurs.

Ram Fault. This bit is active after new configuration information has
been downloaded but not saved in non-volatile memory. Performing the
“Write EEPROM” function will clear this fault.