Reset
This button resets the alarm condition when latching operation is select-
ed.

Start Oi Test
This button initiates a manual Oi test on the selected channel. The test
will run for a pre-determined time and end automatically. If the detector
fails the test, the UV or IR manual Oi fault bit is set.

Fetch Logs
This button will retrieve the alarm logs.

Display UV/IR
This button toggles the bar graph display between UV and IR.

Extended Status
Pressing this button will retrieve additional fault diagnostic information
from the detector. See Figure VII-12. This information can be used to find
the source of the problem when the UV or IR fault indicators are on.

UV Automatic Oi Fault. This indicator is on when the UV detector
has failed the automatic Oi test. To correct the problem, clean the detec-
tor viewing window and Oi ring. The fault will self-clear after the detec-
tor passes three consecutive automatic Oi tests.

UV Manual Oi Fault. This indicator turns on after an unsuccessful
manual Oi test. The fault will clear after a successful test is completed.