Missing UV Tube Fault. When automatic Oi is turned off, the detec-
tor will perform an initial automatic Oi test on power-up. This test
ensures that the UV tube module is properly installed and operating. The
indicator turns on if the detector fails the test. The fault is latching and
can be cleared with a successful manual Oi test.

290 Volt Fault. This indicator turns on when the UV tube module high
voltage power supply is not within the allowed tolerance.

Manual UV Oi Test Active. This bit is set while a manual Oi test is
in progress.

IR Automatic Oi Fault. This indicator is on after the IR detector has
failed the automatic Oi test. To correct the problem, clean the detector
viewing window and Oi ring. The fault will self-clear after the detector
passes three consecutive tests. If the fault continues to occur, the IR Oi
threshold may require adjustment.

IR Manual Oi Fault. This indicator turns on when an unsuccessful
manual Oi test is conducted. The fault will clear after a successful test is
completed.

Missing IR Module. On power-up, the detector looks for background
signal from the IR detector. This ensures that the IR module is properly
installed and operating.

Manual IR Oi Test Active. This bit turns on while a manual Oi test
is in progress.

From the Point Configuration screen, highlight the ARM, then click on
Display Point or select Point from the View menu. The ARM Point Display
screen will be displayed. See Figure VII–13.

S

TATUS

I

NDICATORS

Low Voltage. This indicator turns on when the input power voltage to
the ARM is below 17.5 volts.

Com 1 / Com 2. One of these bits is set when the ARM’s fault isola-
tion circuitry has detected and isolated a LON wiring fault.

7.22

E

AGLE

Q

UANTUM

P

OINT

D

ISPLAYS

A

GENT

R

ELEASE

M

ODULE

(ARM) P

OINT

D

ISPLAY