CRC (Cyclical Redundancy Check) is an error checking method. This
field is incremented when the calculated CRC value is different than the
transmitted value. This error is typically caused by incorrect serial com-
munication settings.

Data. This field tracks the number of response messages that have the
wrong data size.

Com. This field tracks the number of serial communication errors report-
ed by the operating system.

Command. This field tracks the number of Modbus error responses.
This can occur if the gateway is not configured properly. Check the set-
ting of the Main/Aux gateway DIP switch.

Timeouts. This number is incremented each time the gateway does not
respond to the message from the OIS.

When correct communication is established, the read and write counts
should match, with zeros displayed in the Error boxes.

B

UTTONS

Close closes this window.

Add creates a new LON.

Cancel cancels the entry.

Reset Counts resets the counters.

Delete deletes the LON.

Refer to “Device Trigger Configuration” in “Section V — Eagle Quantum
System Configuration” for complete information regarding trigger lists.

Addresses 1 through 4 are reserved for gateways only. Address num-
ber 1 should be used for the main gateway and 2 to 4 for auxiliary
gateways (if used).

1. Highlight line 1 on the Point Configuration screen. Click on the

Modify Point button.

2. Click on the Define button. Select the gateway type, then click on

OK. The Gateway Configuration screen will be displayed. See
Figure VI–1.