Output Active. This indicator turns on while the output circuit is
active.

Output Open. This indicator turns on when the output circuit is not
properly terminated. A wire could be open or the device being moni-
tored could be defective.

Output Isolated. This bit is set when the output circuit has been
instructed to enter the Isolate mode. In this condition, the ARM output cir-
cuit is shorted to ensure that no voltage is present on the output. This
mode is utilized when maintenance is performed on the release circuit.

Auto Config Fault. This bit indicates that the gateway was unable to
successfully download configuration information.

Low Aux Voltage. This indicator turns on when the auxiliary input
voltage is below the specified limit. This fault is self-clearing when the
correct auxiliary power input voltage is applied.

R

ELEASE

M

ODE

This field identifies the output mode that is currently configured.

R

ELEASE

T

IME

When timed mode is used, this field shows how long the release will
continue.

A

LARM

A

DDRESS

This area shows the address of the logic controller that is configured for
communication with this ARM. All trouble status information will be sent
to the address listed here. The address can be changed on the ARM
configuration screen. It is important to ensure that the logic controller is
configured to communicate with this device.

A

LARM

H

ISTORY

The ARM stores the time and date of the last eight activations. This infor-
mation is displayed by pressing the Fetch Logs button.

U

PDATE

R

ATE

This field shows in milliseconds how often the ARM will report its status
to the gateway. The update rate is programmable from 1 to 10 seconds
on the ARM configuration screen.

7.24

E

AGLE

Q

UANTUM

P

OINT

D

ISPLAYS