6. Enter a starting and an ending address for each of the four gateway

relays. These numbers identify a specific “block” of addresses that
will be monitored by each gateway relay. Then check the appropri-
ate boxes to select the event(s) that will actuate each of the relays.
The fault relay will be actuated upon detection of a LON fault (LON
open or shorted) or an internal gateway fault (self-diagnostic test
failure).

7. Check the appropriate “Energized” button if a normally energized

relay coil is desired. The coil will become de-energized when the
relay status becomes active.

8. Checking the Automatic Device Configuration box will cause all

configuration information to remain in effect after the replacement of
an electronic module or an entire field device. This will allow field
device replacement or repair without the need for operator initiated
re-configuration, however, all DIP switches on the replacement
device must be set exactly the same as the original. (This feature is
available for Eagle Quantum systems only.)

9. Click on Accept. Click on Close to exit and return to the Point

Configuration screen, or use the scroll arrows to select the next point
for configuration.

L

OGIC

C

ONTROLLER

B

ASE

C

ONFIGURATION

1. Highlight line 5 on the Point Configuration screen. Click on the

Modify Point button. Click on the Define button. Select Logic
Controller, then click on OK. The Logic Controller Configuration
screen will be displayed. See Figure V–4.

5.6

E

AGLE

Q

UANTUM

S

YSTEM

C

ONFIGURATION

FIGURE V-4

Logic Controller
Configuration Screen