Low Voltage. This bit is set when the input power voltage to the relay
node is below 17.5 volts. The actual voltage can be read from the
“Network” screen.

Unable to Configure. This bit is set by the gateway when it is unable
to successfully transfer configuration information to the relay node.

Output Relay Active. This bit is set when the relay node’s output
relay is activated.

Inhibit. This bit indicates that the gateway relays and display are inhib-
ited from responding to changes in the relay node’s status. The Inhibit
status is controlled by the “Inhibit” button.

Not Communicating. This bit is set by the gateway when its diag-
nostic routine indicates that it has not received periodic status messages
from the relay node. The bit is cleared when a new status update is
received.

Invalid Configuration. This bit indicates that configuration informa-
tion is invalid and is set on a new unit, when the address is changed,
or when invalid data is transferred. A valid configuration must be down-
loaded to clear the bit.

Force On. This bit indicates that the relay is in a “force on” condition,
causing it to be in its active state, regardless of voting or other pro-
grammed responses.

Force Off. This bit indicates that the relay is in a “force off” condition,
causing it to be in its inactive state, regardless of voting or other pro-
grammed responses.

A

LARM

H

ISTORY

The relay node stores and displays the last eight alarms (high and low).
The display includes the type of alarm and the time and date stamp.

B

UTTONS

Reset. This button resets the relay node’s output relay.

Fetch Logs. This button will retrieve the alarm logs.

95-8479

8.7

E

AGLE

2000 P

OINT

D

ISPLAYS