Silence. The silence status bit is set after the Silence switch on the logic
controller faceplate is activated. It indicates that the operator has
silenced the external horns. The bit is latching and will remain set until
the logic controller is reset.

Isolated. The isolated status bit indicates that the logic controller key
switch is in the Isolate position. The Isolate function is provided to aid in
maintenance of releasing type outputs. The operator must provide cus-
tom logic to send this signal to agent release output devices in the field.

Program Mode. This bit indicates that the logic controller is in the
Program mode and is ready to receive configuration information. The
fixed fire and operator logic is stopped in this mode.

Inhibit Active. This bit indicates that the gateway relays and display
are inhibited from responding to changes in the logic controller’s status.
The status is controlled by the “Inhibit” button.

EEPROM Write. This bit indicates that configuration information is cur-
rently being copied from RAM memory to non-volatile memory. This is
initiated by the operator after new configuration information is down-
loaded in the logic controller.

GW LON Fault. This bit is set when the logic controller receives a
LON fault message from the gateway. The gateway will set this bit when
the LON is open and clear it when it is closed. This is done to allow the
logic controller to signal trouble in the event of a LON fault.

P

OWER

S

UPPLY

F

AULTS

AC Failed. The AC Failed fault bit is set when any of the
EQ2100LCUPS power supplies has low or missing AC input voltage.

Power Trouble. The power trouble bit is set when a general power
related fault has been detected.

Power Supply Fault. This bit signals a problem with the
EQ2100LCUPS Power Supply. The bit is latching and remains set until
the logic controller is reset.

Battery Fault. This bit is set when any of the EQ2100LCUPS power
supplies has low or missing batteries.

IO F

AULTS

All IO Faults relate to the EQ2100LCUPS power supplies or
EQ2100LIOU devices.

7.6

E

AGLE

Q

UANTUM

P

OINT

D

ISPLAYS

Advertising