Det-Tronics EagleVision - PC User Manual

Page 88

Advertising
background image

I

NDICATORS

Upper Xcever Fault and Lower Xcever Fault. These bits indi-
cate that the self-diagnostic tests have detected a malfunction in one of
the LON communication transceivers. Reset the gateway by cycling
power. If the fault continues, replace the gateway.

Gateway Fault. This bit is set when the self-diagnostic test has detect-
ed an internal problem with the gateway. Reset the gateway by cycling
power. If the fault continues, replace the gateway.

LON Relay Override. This bit indicates that the user has overridden
the normal function of the gateway’s LON relay. The LON relay is used
to connect the ends of the network in the event of a LON fault. While
troubleshooting, it is helpful to override the automatic function of this
relay. However, it is critical to return the relay to the automatic mode
after troubleshooting is completed.

Invalid Configuration. This bit indicates that the gateway has not
been configured or that the configuration does not match the DIP switch
settings.

Unable to Configure. The main gateway was unable to successfully
transfer configuration data to an auxiliary gateway.

Not Communicating. This bit is set when any configured gateways
fail to report on schedule.

8.2

E

AGLE

2000 P

OINT

D

ISPLAYS

FIGURE VIII-1

Eagle 2000 Gateway
Point Display Screen