To determine the location of a wiring fault on the network:

From the Point Configuration screen, click on the Overview button to dis-
play the System Overview screen. This screen provides an overview of
the entire system. Each configured node is represented by a square on
the loop, and is identified by its address number. The color or the square
indicates the status condition.

Black =

Normal operation

Red =

Alarm

Yellow = Fault condition.

Click on the LON Diag. button. The LON Diagnostic screen is dis-
played. See Figure IX-1.

In the LON diagnostic mode, each node changes color as it reports to
the gateway at the update rate determined at the time of configuration.
This continual change in color indicates that normal LON communica-
tion is occurring. The color of the node indicates which of the gateway’s
two transceivers is receiving the message — green = LON 1, blue =
LON 2, red = no communication. (The three boxes in the lower right
hand corner of the screen are not buttons, but represent the gateway
transceiver color code.)

95-8479

9.1

LON T

ROUBLESHOOTING

FIGURE IX-1

LON Diagnostic Screen