6. Enter a starting and an ending address for each of the four gateway

relays. These numbers identify a specific “block” of addresses that
will be monitored by each gateway relay. Then check the appropri-
ate boxes to select the event(s) that will actuate each of the relays.
The fault relay will be actuated upon detection of a LON fault (LON
open or shorted) or an internal gateway fault (self-diagnostic test
failure).

7. Check the appropriate “Energized” button if a normally energized

relay coil is desired. The coil will become de-energized when the
relay status becomes active.

8. Click on Accept. Click on Close to exit and return to the Point

Configuration screen, or use the scroll arrows to select the next point
for configuration.

1. Highlight the desired address on the Point Configuration screen.

Click on the Modify Point button.

2. Click on the Define button.

3. Click on the Communication Module button, then click on OK. The

Communication Module Point Configuration screen will be dis-
played. See Figure VI–2.

6.4

E

AGLE

2000 S

YSTEM

C

ONFIGURATION

C

OMMUNICATION

M

ODULE

C

ONFIGURATION

FIGURE VI-2

Communication Module
Point Configuration Screen