Technical data, 600vac models – Lenze ESV SMV frequency inverter User Manual

Page 13

Advertising
background image

Lenze SMVector 13465100 EDBSV01 EN v18

11

Technical Data

600VAC Models

600V Three Phase (3/PE) (425...660V); 48...62Hz

Type

Power

Mains Current

Output Current

Heat Loss (Watts)

Hp

kW

A

Cont (I

n

)

A

Max I

%

N1/IP31

N4X/IP65

No filter

N4X/IP65

W/ filter

ESV751--6T--

1

0.75

2

1.7

200

37

31

ESV152--6T--

2

1.5

3.2

2.7

200

51

43

ESV222--6T--

3

2.2

4.4

3.9

200

68

57

ESV402--6T--

5

4

6.8

6.1

200

101

67

ESV552--6T--

7.5

5.5

10.2

9

200

148

116

ESV752--6T--

10

7.5

12.4

11

200

172

152

ESV113--6T--

15

11

19.7

17

180

380

356

ESV153--6T--

20

15

25

22

180

463

431

ESV183--6T--

25

18.5

31

27

180

560

519

ESV223--6T--

30

22

36

32

180

640

592

ESV303--6T--

40

30

47

41

180

930

ESV373--6T--

50

37.5

59

52

180

1163

ESV453--6T--

60

45

71

62

180

1395

NOTES:
Output Current: The Output Current Maximum (%) is a percentage of the Output Current Continuous Amps (In) rating
and is adjustable in parameter P171.

STOP!

• For installations above 1000m a.m.s.l., derate I

n

by 5% per 1000m, do not

exceed 4000m a.m.s.l.

• Operation above 40°C, derate I

n

by 2.5% per °C, do not exceed 55°C.

Output Current (In) derating for Carrier Frequency (P166) for NEMA 1 (IP31) Models:

- If P166=2 (8 kHz), derate I

n

to 92% of drive rating

- If P166=3 (10 kHz), derate I

n

to 84% of drive rating

Output Current (In) derating for Carrier Frequency (P166) for NEMA 4X (IP65) Models:

- If P166=1 (6 kHz), derate I

n

to 92% of drive rating

- If P166=2 (8 kHz), derate I

n

to 84% of drive rating

- If P166=3 (10 kHz), derate I

n

to 76% of drive rating

Advertising