Installation, 3 control terminals – Lenze ESV SMV frequency inverter User Manual

Page 23

Advertising
background image

Lenze SMVector 13465100 EDBSV01 EN v18

21

Installation

Notes for Fuse and Cable Table:
(1) Installations with high fault current due to large supply mains may require a type D circuit breaker.

(2) UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, preferred. Bussman KTK-R, JJN or JJS or equivalent.

(3) Thermomagnetic type breakers preferred.

_ 11th digit of part number:

F = Integral EMC Filter

L = Integral EMC Filter and Integrated Disconnect Switch (NEMA 4X/IP65 Models only)

M = Integrated Disconnect Switch (NEMA 4X/IP65 Models only)

X = No EMC Filter/ No Disconnect Switch

* = Last digit of part number: C = N4X Indoor only (convection cooled)

E = N4X Indoor/Outdoor (convection cooled)

~ = Last digit of part number: D = N4X Indoor only (fan cooled)

F = N4X Indoor/Outdoor (fan cooled)

Observe the following when using Ground Fault Circuit Interrupters (GFCIs):

• Installation of GFCI only between supplying mains and controller.
• The GFCI can be activated by:

- capacitive leakage currents between the cable screens during operation (especially with long, screened motor cables)
- connecting several controllers to the mains at the same time
- RFI filters

3.2.3

Control Terminals

Control Terminal Strip for 0.33 - 10 HP (0.25 - 7.5 kW):

6 25 4 11 13A 13B 13C

17

5

1 2

14 30 16

AOUT

DIGOUT

2k … 10k

+10 V

AIN

AIN

COM

COM

ALsw

25

2

4 … 20 mA

5

2

0 … 10 V

1 2 4 13A 13B 13C

+12 VDC - 0 %

. . .

+30 VDC + 0 %

ALsw

+15V

1 2 4 13A 13B 13C

ALsw

COM

PNP

NPN

4.5 lb-in

(0.5 Nm)

0.25 in (6 mm)

AWG 26…16

(<1mm²)

Control Terminal Strip for 15HP (11 kW) and Greater Drives:

6 25 4 11 13A13B 13C

TXA

5

1 2

14 30 2

AOUT

DIGOUT

2k … 10k

+10

V

+12

V

AIN

AIN

COM

COM

ALsw

17

16

TXB

13D

13D

13D

25

2

4 … 20 mA

5

2

0 … 10 V

1 2 4 13A 13B 13C

+12 VDC - 0 %

. . .

+30 VDC + 0 %

ALsw

+15V

1 2 4 13A 13B 13C

ALsw

COM

4.5 lb-in

(0.5 Nm)

0.25 in (6 mm)

AWG 26…16

(<1mm²)

NOTE

Control and communications terminals provide basic insulation when the drive is connected to a power system rated up
to 300V between phase to ground (PE) and the applied voltage on terminals 16 and 17 is less than 250 VAC between
phase to phase and ground (PE).