Commissioning – Lenze ESV SMV frequency inverter User Manual

Page 56

Advertising
background image

54

Lenze SMVector 13465100 EDBSV01 EN v18

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P794

End Segment: TB30
Analog Output
Value

0.00

0.00

{VDC} 10.00

TB30 configuration parameter must be set to
accept this value: P150 = 10

P795

End Segment:
Drive Action

0

0 Keep Running

Recovery: Toggling the START SEQUENCE will
start the cycle from ‘end segment Stop’ or ‘end
segment DC Brake’.

1 Stop (based on P111)
2 Coast to Stop
3 Quick Stop (per P127)
4 Coast with DC Brake
5 Ramp with DC Brake
WARNING!
If P795 = 0 then toggling the start sequence input will also restart the sequencer cycle but
in the interim where TB13X is open the drive will ramp to the standard or specified alternate
speed source depending on the drive configuration.

WARNING
If the input defined to “Start Sequence” is opened during a sequence, the drive will exit sequencer mode
and will run at the specified standard or alternate speed source (dependent on drive configuration).