Commissioning – Lenze ESV SMV frequency inverter User Manual
Page 56

54
Lenze SMVector 13465100 EDBSV01 EN v18
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
P794
End Segment: TB30
Analog Output
Value
0.00
0.00
{VDC} 10.00
TB30 configuration parameter must be set to
accept this value: P150 = 10
P795
End Segment:
Drive Action
0
0 Keep Running
Recovery: Toggling the START SEQUENCE will
start the cycle from ‘end segment Stop’ or ‘end
segment DC Brake’.
1 Stop (based on P111)
2 Coast to Stop
3 Quick Stop (per P127)
4 Coast with DC Brake
5 Ramp with DC Brake
WARNING!
If P795 = 0 then toggling the start sequence input will also restart the sequencer cycle but
in the interim where TB13X is open the drive will ramp to the standard or specified alternate
speed source depending on the drive configuration.
WARNING
If the input defined to “Start Sequence” is opened during a sequence, the drive will exit sequencer mode
and will run at the specified standard or alternate speed source (dependent on drive configuration).