Commissioning, 1 terminal & protection status display, 2 keypad status display – Lenze ESV SMV frequency inverter User Manual

Page 47

Advertising
background image

Lenze SMVector 13465100 EDBSV01 EN v18

45

Commissioning

Code

Display Range (READ ONLY)

IMPORTANT

No.

Name

p560

Sequencer: Currently
Active Segment

0 17

p561

Sequencer: Time
since Start of Active
Segment

0.0

{P708} 6553.5

0

{P708} 65535

Unit depends on P708 (0.1sec, sec or minutes)

p562

Sequencer: Time
Remaining in Active
Segment

0.0

{P708} 6553.5

0

{P708} 65535

Unit depends on P708 (0.1sec, sec or minutes)

p563

Sequencer: Number
of cycles since start

0 65535

p564

Sequencer: Number
of cycles remaining

0 65535

NOTE: Parameters P560-P564 are visible only when P700 > 0 (i.e. the sequencer is enabled)

4.5.7.1 Terminal & Protection Status Display

Parameter P530 allows monitoring of the control terminal
points and common drive conditions:
An illuminated LED segment indicates:

• the protective circuit is active (LED 1)
• the Logic Assertion Switch is set to High (+)
• input terminal is asserted (LED 2)
• output terminal is energized (LED 4)
• the Charge Relay is not a terminal, this segment will

be illuminated when the Charge Relay is energized
(LED 4).

4.5.7.2 Keypad Status Display

Parameter P531 allows monitoring of the keypad
pushbuttons:
An illuminated LED segment indicates when the button is
depressed.

LED 1 and LED 2 are used to indicate pushbutton presses on
a remote keypad that is attached to the drive. LED 3 and LED
4 indicate button presses on the local drive keypad.

Input 13C
Input 13A
Factory Reserved
Protective Diagnostic

Current Limit Diagnostic
Logic Assertion Switch
Input 1
Input 13B
Relay
Output 14

Input 13D*

* Input 13D available on 15-60HP (11-45kW) models only

LED #

1

2

3

4

Charge
Relay

Auxiliary Relay
Input 13F
Input 13E

Additional I/O Module only

CTRL