Commissioning – Lenze ESV SMV frequency inverter User Manual

Page 38

Advertising
background image

36

Lenze SMVector 13465100 EDBSV01 EN v18

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P164

TB-25 (4-20mA)
Analog Input
Monitoring Level

2.0

0.0

{mA} 20.0

P165

Base Voltage

15 {V} 1000

Valid for V/Hz mode only.
Set voltage for bus compensation in V/Hz mode

P166

Carrier Frequency

See

Notes

0 4 kHz

• As carrier frequency is increased, motor noise

is decreased

• Observe derating in section 2.3
• Automatic shift to 4 kHz at 120% load
• NEMA 4X (IP65) Models: Default = 0 (4kHz)
• NEMA 1 (IP31) Models: Default = 1 (6kHz)

1 6 kHz
2 8 kHz
3 10 kHz

p167

(1)

Base Frequency

60.0

10.0 {Hz} 1500

V0112

p168

Fixed Boost

0.0

{%} 40.0

NOTE
• P167 = rated motor frequency for standard applications
• P165, P168 = default setting depends on drive rating

p169

Accel Boost

0.0

0.0

{%} 20.0

Accel Boost is only active during acceleration

P170

Slip Compensation

0.0

0.0

{%} 40.0

Increase P170 until the motor speed no longer
changes between no load and full load conditions.

p171

(1)

Current Limit

Max I

30

{%}

Max I

• When the limit is reached, the drive displays

CL(Current Limit), and either the acceleration

time increases or the output frequency
decreases.

• Digital outputs can also indicate when the limit

is reached; see P140, P142.

• Refer to section 2.3 for the maximum output

current Max I (%)

P172

Current Limit
Reduction

0

0 Current Limit Reduction Active -

Normal response

In field weakening, the Current Limit is inversely
proportional to the speed.

1 Current Limit Reduction Active - Fast

response

2 Current Limit Reduction Disabled -

Normal response

3 Current Limit Reduction Disabled -

Fast response

P173

Decel Override Time

2.0

0.0 {s} 60.0

Maximum time before drive trips into HF fault.

P174

DC Brake Voltage

0.0

0.0

{%} 50.0

Setting is a percent of the nominal DC bus voltage.

(1)

Any changes to this parameter will not take effect until the drive is stopped.

Advertising