Lenze SMVector 13465100 EDBSV01 EN v18

Troubleshooting and Diagnostics

5

Troubleshooting and Diagnostics

5.1

Status/Warning Messages

Status / Warning

Cause

Remedy

br

DC-injection brake active

DC-injection brake activated
• activation of digital input

(P121...P124 = 18)

• automatically (P110 = 2, 4...6)
• automatically (P111 = 1, 3)

Deactivate DC-injection brake
• deactivate digital input

• automatically after P175 time has

expired

bf

Drive ID warning

The Drive ID (P502) stored on the EPM
does not match the drive model.

• Verify motor data (P302…P306) and

perform Auto Calibration.

• Set drive mode (P300) to 0 or 1
• Reset the drive (P199 to 3 or 4) and

reprogram.

CAL

Motor Auto-calibration active

Refer to P300, P399

Motor Auto-calibration is being performed

cE

An EPM that contains valid data from
a previous software version has been
installed

An attempt was made to change
parameter settings

Parameter settings can only be changed after
the EPM data is converted to the current
version (P199 = 5)

CL

Current Limit (P171) reached

Motor overload

• Increase P171
• Verify drive/motor are proper size for

application

deC

Decel Override

The drive has stopped decelerating
to avoid tripping into HF fault, due to

excessive motor regen (2 sec max).

If drive trips into HF fault:

• Increase P105, P126
• Install Dynamic Braking option

Err

Error

Invalid data was entered, or an invalid
command was attempted

FCL

Fast Current Limit

Overload

Verify drive/motor are proper size for
application

fst

Flying Restart Attempt after Fault

P110 = 5,6

GE

OEM Settings Operation warning

An attempt was made to change
parameter settings while the drive is
operating in OEM Settings mode.

In OEM Settings mode (P199 = 1), making
changes to parameters is not permitted.

GF

OEM Defaults data warning

An attempt was made to use (or reset to)
the OEM default settings (P199 = 1 or 2)
using an EPM without valid OEM data.

Install an EPM containing valid OEM Defaults
data

LC

Fault Lockout

The drive attempted 5 restarts after a
fault but all attempts were unsuccessful
(P110 = 3...6)

• Drive requires manual reset
• Check Fault History (P500) and correct

fault condition

PdeC

PID Deceleration Status

PID setpoint has finished its ramp but
the drive is still decelerating to a stop.

PID

PID Mode Active

Drive has been put into PID Mode.

Refer to P200

SLP

Sleep Mode is active

Refer to P240...P242

SP

Start Pending

The drive has tripped into a fault and
will automatically restart (P110 = 3...6)

To disable Auto-Restart, set P110 = 0...2

spd

PID Mode disabled.

Drive has been taken out of PID Mode.
Refer to P200.

stoP

Output frequency = 0 Hz
(outputs U, V, W inhibited)

Stop has been commanded from the
keypad, terminal strip, or network

Apply Start command (Start Control source
depends on P100)

(1)

The drive can only be restarted if the error message has been reset.