Installation – Lenze ESV SMV frequency inverter User Manual

Page 24

Advertising
background image

22

Lenze SMVector 13465100 EDBSV01 EN v18

Installation

Control Terminal Strip Descriptions

Terminal Description

Important

1

Digital Input: Start/Stop

input resistance = 4.3k

W

2

Analog Common

5

Analog Input: 0...10 VDC

input resistance: >50 k

W

6

Internal DC supply for speed pot

+10 VDC, max. 10 mA

25

Analog Input: 4...20 mA

input resistance: 250

W

4

Digital Reference/Common

+15 VDC / 0 VDC, depending on assertion level

11

Internal DC supply for external devices

+12 VDC, max. 50 mA

13A

Digital Input: Configurable with P121

input resistance = 4.3k

W

13B

Digital Input: Configurable with P122

13C

Digital Input: Configurable with P123

13D*

Digital Input: Configurable with P124

14

Digital Output: Configurable with P142, P144

DC 24 V / 50 mA; NPN

30

Analog Output: Configurable with P150…P155

0…10 VDC, max. 20 mA

2*

Analog Common

TXA*

RS485 TxA

TXB*

RS485 TxB

16

Relay output: Configurable with P140, P144

AC 250 V / 3 A
DC 24 V / 2 A … 240 V / 0.22 A, non-inductive

17

* = Terminal is part of the terminal strip for the 15HP (11kW) and higher models only.

Assertion level of digital inputs
The digital inputs can be configured for active-high or active-low by setting the Assertion Level Switch (ALsw) and P120.
If wiring to the drive inputs with dry contacts or with PNP solid state switches, set the switch and P120 to “High” (+). If
using NPN devices for inputs, set both to “Low” (-). Active-high (+) is the default setting.

HIGH = +12 … +30 V
LOW = 0 … +3 V

NOTE
An F_AL fault will occur if the Assertion Level switch (ALsw) position does not match the parameter
P120 setting and P100 or any of the digital inputs (P121...P124) is set to a value other than 0.