Commissioning – Lenze ESV SMV frequency inverter User Manual

Page 40

Advertising
background image

38

Lenze SMVector 13465100 EDBSV01 EN v18

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

p190

Motor Braking

0 Disabled

Flux brake OFF.

1 Braking with BUS threshold

When drive is in deceleration and V

bus

> V

deceleration freeze

(114% of

the rated V

bus

), the flux brake will be turned ON.

2 Braking always on with deceleration

As long as drive is in deceleration, the flux brake will be ON.

3 Braking with bus regulator

When drive is in deceleration and V

bus

> V

deceleration freeze

(114%

of the rated V

bus

), the motor speed will be increased to reduce

the bus voltage. Determined by the value in P191, the speed
increment = slip speed * P191(%) / 37.

4 Special

(Consult factory before using)

WARNING
Flux braking can cause heat in the motor. To avoid damage to the motor, use a PTC to
protect the motor. If the flux brake is used too frequently, the drive will trip fault “F_PF”.

p191

Motor Brake Level

0

0

{%}

75

(flux
braking
disabled)

Active when P190 > 0 and drive is in deceleration

mode. Use to reduce deceleration time on high
inertia loads.

NOTE: Over usage of P190 can cause frequent

‘overload’ trips “F.PF”

Not active for P300 = 5 (Torque mode)

p192

Motor Braking
Deceleration
Reduction Level

0.0

0 P167

(base freq)

Raising the value of P191 reduces the
drive deceleration rate during flux braking.

Active when P190 > 0 and P192 > 0.0, Drive is

in deceleration mode. Use to reduce deceleration
time on high inertia loads.

NOTE: Usage of P192 can cause the drive to

decelerate faster than settings in P105/P127.

Not active for P300 = 5 (Torque mode)

P194

Password

0

0000 9999

• Must enter password to access parameters
• P194 = 0000: Disables password

P197

Clear Fault History

0

0 No Action
1 Clear Fault History

p199

Program Selection

0 Operate from User settings
1 Operate from OEM settings

Refer to Notes 1, 2 and 3

2 Reset to OEM default settings

Refer to Note 1

3 Reset to 60 Hz default settings

• Refer to Note 4
• Parameters are reset to the defaults listed in

this manual.

• For P199=4, the following exceptions apply:

- P103, P152, P161, P167 = 50.0 Hz
- P165 = 400V (400/480V drives only)
- P304 = 50 Hz
- P305 = 1450 RPM
- P107 = 0 (480 V drives only)

4 Reset to 50 Hz default settings

5 Translate

Refer to Note 5

WARNING!
Modification of P199 can affect drive functionality! STOP and EXTERNAL FAULT circuitry may
be disabled! Check P100 and P121...P124
NOTE 1
If the EPM does not contain valid OEM settings, a flashing GF will be displayed when P199

is set to 1 or 2.
NOTE 2
When P199 is set to 1, the drive operates from the OEM settings stored in the EPM Module
and no other parameters can be changed (GE will be displayed if attempted).

NOTE 3
Auto Calibration is not possible when operating from OEM Settings.
NOTES 4 and 5 - on next page.