Lenze SMVector 13465100 EDBSV01 EN v18

33

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

p140

Relay Output
TB-16, 17

0

0 None

Disables the output

1 Run

Energizes when the drive is running

2 Reverse

Energizes when reverse rotation is active

3 Fault

De-energizes when the drive trips, or power is
removed

4 Inverse Fault

Energizes when the drive trips

5 Fault Lockout

P110 = 3...6: De-energizes if all restart attempts
fail

6 At Speed

Energizes when output frequency = commanded
frequency

7 Above Preset Speed #6

Energizes when output frequency > P136

8 Current Limit

Energizes when motor current = P171

9 Follower Loss (4-20 mA)

Energizes when 4-20 mA signal is < P164

10 Loss of Load

Energizes when motor load drops below P145;
Refer to P146 also

11 Local Keypad Control Active

Energizes when the selected source is active for
start control

12 Terminal Strip Control Active
13 Remote Keypad Control Active
14 Network Control Active
15 Standard Reference Active

Energizes when P101 reference is active

16 Auto Reference Active

Energizes when Auto Reference is activated using
TB-13 input; refer to P121...P124

17 Sleep Mode Active

Refer to P240...P242

18 PID Feedback < Min. Alarm

Energizes when PID feedback signal < P214

19 Inverse PID Feedback < Min. Alarm De-energizes when PID feedback signal < P214
20 PID Feedback > Max Alarm

Energizes when PID feedback signal > P215

21 Inverse PID Feedback > Max Alarm De-energizes when PID feedback signal > P215
22 PID Feedback within

Min/Max Alarm range

Energizes when PID feedback signal is within the
Min/Max Alarm range; refer to P214, P215

23 PID Feedback outside

Min/Max Alarm range

Energizes when PID feedback signal is outside the
Min/Max Alarm range; refer to P214, P215

24 Reserved
25 Network Controlled

SMV models < 15HP (11kW) require an optional
communication module (refer to the network
module documentation).

26 Loss of 0-10V Input

Energizes when 0-10V signal is < P158

27 Sequencer Controlled

State set in individual sequencer segments

28 Sequencer Active
29 Sequencer Suspended
30 Sequence Done

End Sequence

31 Output Frequency = 0.0Hz

Output inactive

p142

TB-14 Output

0

0...23 (same as P140)
24 Dynamic Braking

For use with Dynamic Braking option

25...31 (same as P140)