42

Lenze SMVector 13465100 EDBSV01 EN v18

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

p304

(1)

Motor Rated
Frequency

60

0

{Hz} 1000

Set to motor nameplate data

P305

(1)

Motor Rated Speed

1750

300

{RPM} 65000

P306

(1)

Motor Cosine Phi

0.80

0.40 0.99
NOTE If motor cosine phi is not known, use one of the following formulas:
cos phi = motor Watts / (motor efficiency X P302 X P303 X 1.732)
cos phi = cos [ sin

-1

(magnetizing current / motor current) ]

P310

(1)

Motor Stator
Resistance

0.00 {

W} 64.00

• P310, 311 default setting depends on drive rating
• Will be automatically programmed by P399
• Changing these settings can adversely affect

performance. Contact factory technical support
prior to changing

p311

(1)

Motor Stator
Inductance

0.0

{mH} 2000

P315

Dead Time
Compensation Factor

0.0

-50.0 {%} +50.0

• Adjust dead time correction from internal default
• Takes effect when P399 = 3.

P330

Torque Limit

100

0

{%} 400

When P300 = 5, sets the maximum output torque.

P331

Preset Torque
Setpoint #1

100

0

{%} 400

TB-13A activated; P121 = 3 and P300 = 5

P332

Preset Torque
Setpoint #2

100

0

{%} 400

TB-13B activated; P122 = 3 and P300 = 5

P333

Preset Torque
Setpoint #3

100

0

{%} 400

TB-13C activated; P123 = 3 and P300 = 5

P334

(2)

Preset Torque
Setpoint #4

100

0

{%} 400

TB-13D activated; P124 = 3 and P300 = 5

P340

(1)

Current Loop P Gain

0.25

0.00 16.0

Changing these settings can adversely affect
performance. Contact factory technical support
prior to changing.

P341

(1)

Current Loop I Gain

65

12

{ms} 9990

P342

(1)

Speed Loop Adjust

0.0

0.0

{%} 20.0

P343

Slip Compensation
Response Filter

99

90

{ms} 9999

Low pass filter time constant for varying the slip
compensation response to changes in the motor
current.

P399

Motor Auto-
calibration

0

0 Calibration Not Done

• If P300 = 4 or 5, motor calibration must be

performed if P399 is not set to 3 (bypass
calibration).

• If P300=2 or 3, motor calibration is

recommended.

• Use option 2 if option 1 failed or in case of non-

standard motors

• An alternating CAL / Err will occur if:

- attempt motor calibration with P300 = 0 or 1
- motor calibration is attempted before

programming motor data

1 Standard Calibration Enabled
2 Advanced Calibration Enabled
3 Bypass Calibration, enable

operation in vector mode w/o Auto
Calibration

4 Standard Calibration Complete
5 Advanced Calibration Complete

NOTE: To run the Auto Calibration:

− Set P302...P306 according to motor nameplate

− Set P399 = 1 or 2 (if option 1 failed or in case of non-standard motor)

− Make sure motor is cold (20° - 25° C)

− Apply a Start command

− Display will indicate CAL for about 40 seconds

− Once the calibration is complete, the display will indicate Stop; apply another

Start command to actually start the motor

− Parameter P399 will now be set to 4 or 5.

(1)

Any changes to this parameter will not take effect until the drive is stopped.

(2)

Parameter applicable to SMV models 15HP (11kW) and higher.