Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P144

Digital Output
Inversion

P144

Invert

P142

Invert

P140

0

NO

NO

1

NO

YES

2

YES

NO

3

YES

YES

Used to invert the selections for P140 (Relay Output)
and P142 (TB-14 Output).
EXAMPLE: When P140 = 6 (AT SPEED), the relay is
energized when output frequency = commanded
frequency. IF P144=1 or 3, then P140 is inverted
(INVERSE AT SPEED) and the relay is energized
when the output frequency does

not equal the

command frequency.

NOTE
Inverting P140 or P142 when the parameter is set to NONE (0) will result in the output being
energized continuously.
NOTE
For SMVector drives rated at 0.33 to 10 HP (0.25 to 7.5 kW), P144 is only available with
software versions 3.0 and higher (refer to P501).

p145

Loss of Load
Threshold

0

0

{%} 200

P140, P142 = 10: Output will energize if motor
load falls below the P145 value longer than the
P146 time

p146

Loss of Load Delay

0.0

0.0 {s} 240.0

p149

Analog Output Offset

0.0

0

{%} 100

Scaled value. Example: P149 = 10%, Scaled
variable = freq, P150 = 1, P152 = 60Hz; then
TB30 = 0VDC below 6Hz

p150

TB-30 Output

0

0 None

2-10 VDC signal can be converted to 4-20 mA with
a total circuit impedance of 500

W

1 0-10 VDC Output Frequency
2 2-10 VDC Output Frequency
3 0-10 VDC Load
4 2-10 VDC Load
5 0-10 VDC Torque
6 2-10 VDC Torque
7 0-10 VDC Power (kW)
8 2-10 VDC Power (kW)
9 Network Controlled

SMV models < 15HP (11kW) require an optional
communication module (refer to the network
module documentation).

10 Sequencer Controlled

Value set in individual sequencer segments

p151

Add Analog Input to
TB-30 Output

0

P151

Add TB-25
(4-20mA)

Add TB-5
(0-10VDC)

0

NO

NO

1

NO

YES

2

YES

NO

3

YES

YES

This parameter adds the analog input signal(s) to
the TB-30 Output signal. EXAMPLE: If a drive is
running at 60Hz with P150 set to 1 (0-10VDC Freq)
and P152 set to 240.0Hz, the output at TB-30 would
be 2.5VDC. If there is a 2.0VDC signal going into
TB-5 and P151 is set to 1 (ADD TB-5), the output
at TB-30 would become 4.5VDC.

p152

TB-30 Scaling:
Frequency

60.0

3.0

{Hz} 2000

If P150 = 1 or 2, sets the frequency at which output
equals 10 VDC

p153

TB-30 Scaling: Load

200

10

{%} 500

If P150 = 3 or 4, sets the Load (as a percent of
drive current rating) at which output equals 10 VDC.

p154

TB-30 Scaling:
Torque

100

10

{%} 1000

If P150 = 5 or 6, sets the Torque (as a percent of
motor rated torque) at which output equals 10 VDC

p155

TB-30 Scaling:
Power (kW)

1.0

0.1

{kW} 200.0

If P150 = 7 or 8, sets the power at which output
equals 10 VDC