Commissioning, 4 pid parameters – Lenze ESV SMV frequency inverter User Manual

Page 41

Advertising
background image

Lenze SMVector 13465100 EDBSV01 EN v18

39

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

p199

Program Selection

NOTE 4
Resetting to 50 and 60 Hz default settings will set the Assertion Level (P120) to “2” (High).
P120 may need to be reset for the digital input devices being used. An F.AL fault may occur

if P120 and the Assertion switch are not set identically.
NOTE 5
If an EPM that contains data from a previous compatible software version is installed:
• The drive will operate according to the previous data, but parameters cannot be changed

(cE will be displayed if attempted)

• To update the EPM to the current software version, set P199 = 5. The parameters can now

be changed but the EPM is incompatible with previous software revisions.

4.5.4

PID Parameters

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P200

PID Mode

0

0 Disabled

• Normal-acting: As feedback increases, motor

speed decreases

• Reverse-acting: As feedback increases, motor

speed increases

• PID mode is disabled in Vector Torque mode

(P300 = 5)

• Selections 3, 4: If P112=1, PID controller output

sets the speed, (range -max freq to +max freq)

1 Normal-acting
2 Reverse-acting
3 Normal-acting, Bi-directional
4 Reverse-acting, Bi-directional

NOTE
To activate PID mode, one of the TB-13 inputs (P121...P124) must be used to select the
Auto Reference that matches the desired PID setpoint reference. If the selected PID setpoint
reference uses the same analog signal as the PID feedback (P201), an F.IL fault will occur.

Example: The desired PID setpoint reference is the keypad (p and q). Set TB-13x = 6
(Auto Reference: Keypad):
• TB-13x = closed: PID mode is active
• TB-13x = open: PID mode is disabled and the drive speed will be controlled by the

reference selected in P101.

p201

PID Feedback Source

0

0 4-20 mA (TB-25)

Must be set to match the PID feedback signal

1 0-10 VDC (TB-5)
2 Drive Load (P507)
3 Feedback from Network

p202

PID Decimal Point

1

0 PID Display = XXXX

Applies to P204, P205, P214, P215, P231...P233,
P242, P522, P523

1 PID Display = XXX.X
2 PID Display = XX.XX
3 PID Display = X.XXX
4 PID Display = .XXXX

p203

(2)

PID Units

0

0 %

Select the UNITS LED that will be illuminated when
the drive is running in PID control mode

1 /UNITS
2 AMPS
3 NONE

p204

Feedback at
Minimum Signal

0.0

-99.9 3100.0

Set to match the range of the feedback signal
being used
Example: Feedback signal is 0 - 300 PSI; P204 =
0.0, P205 = 300.0

p205

Feedback at
Maximum Signal

100.0 -99.9 3100.0

(2)

Parameter applicable to SMV models 15HP (11kW) and higher.