Technical Data

2

Technical Data

2.1

Standards and Application Conditions

Conformity

CE

Low Voltage (2006/95/EC) & EMC (2004/108/EC) Directives

Approvals

UL508C

Underwriters Laboratories -Power Conversion Equipment

Input voltage phase imbalance

< 2%

Supported Power Systems

TT
TN

− For central grounded systems, operation is permitted

without restrictions.

− For corner grounded 400/500V systems, operation is

possible but reinforced insulation to control circuits is
compromised.

Humidity

< 95% non-condensing

Temperature range

Transport

-25 … +70°C

Storage

-20 … +70°C

Operation

-10 … +55°C (with 2.5%/°C current derating above +40°C)

Installation height

0 - 4000m a.m.s.l. (with 5%/1000 m current derating above 1000m a.m.s.l.)

Vibration resistance

acceleration resistant up to 1.0g

Earth leakage current

> 3.5 mA to PE

Max Permissable Cable Length

(1)

<= 4.0 Hp (3.0 kW) 30 meters shielded, 60 meters un-shielded

=> 5.0 Hp (3.7 kW) 50 meters shielded, 100 meters un-shielded.

Enclosure

IP31/NEMA 1

IP65/NEMA 4X

NEMA 1 and NEMA 4X model enclosures are plenum rated in accordance with UL
508C and are suitable for installation in a compartment handling conditioned air.

Protection measures against

Earth fault, phase loss, over voltage, under voltage, motor stalling, over temperature
motor overload (125% of FLA), short circuit (SCCR=200kA at rated voltage)

Compliance with EN 61000-3-2
Requirements

(2)

< 0.5kW

with mains choke

0.5 ... 1kW

with active filter

> 1kW

without additional measures

Compliance with EN 61000-3-12
Requirements

(2)

16 ... 75amp

Additional measures required for compliance with EN 61000-3-12

Operation in public supply networks (Limitation of harmonic currents i.a.w. EN 61000-3-2, Electromagnetic Compatibility
(EMC) Limits). Limits for harmonic current emissions (equipment input current up to 16A/phase).

(1) The stated cable lengths are permissible at default carrier frequencies (refer to parameter P166).
(2) The additional measures described only ensure that the controller meets the requirements of the EN 61000-3-2.

The machine/system manufacturer is responsible for the machine’s compliance with the regulations.