Commissioning – Lenze ESV SMV frequency inverter User Manual

Page 42

Advertising
background image

40

Lenze SMVector 13465100 EDBSV01 EN v18

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

p207

Proportional Gain

5.0

0.0

{%} 1000.0

Used to tune the PID loop:
• Increase P207 until system becomes unstable,

then decrease P207 by 10-15%

• Next, increase P208 until feedback matches

setpoint

• If required, increase P209 to compensate for

sudden changes in feedback

p208

Integral Gain

0.0

0.0 {s} 20.0

p209

Derivative Gain

0.0

0.0 {s} 20.0

NOTE

Derivative Gain is very sensitive to noise on the feedback signal. Use with care.

Derivative Gain is not normally required in pump and fan applications

p210

PID Setpoint Ramp

20.0

0.0 {s} 100.0

• time of setpoint change from P204 to P205

or vice versa.

• Used to smooth the transition from one PID

setpoint to another, such as when using the
Preset PID Setpoints (P231...P233)

p214

Minimum Alarm

0.0

P204 P205

Use with P140, P142 = 18...23

P215

Maximum Alarm

0.0

P204 P205

P231

Preset PID Setpoint #1

0.0

P204 P205

TB-13A activated; P121 = 3 and P200 = 1 or 2

P232

Preset PID Setpoint #2

0.0

P204 P205

TB-13B activated; P122 = 3 and P200 = 1 or 2

P233

Preset PID Setpoint #3

0.0

P204 P205

TB-13C activated; P123 = 3 and P200 = 1 or 2

P234

(2)

Preset PID Setpoint #4

0.0

P204 P205

TB-13D activated; P124 = 3 and P200 = 1 or 2

P240

Sleep Threshold

0.0

0.0

{Hz} 500.0

• If drive speed < P240 for longer than P241,

output frequency = 0.0 Hz; drive display = SLP

• P240 = 0.0: Sleep mode is disabled.
• P200 = 0…2: Drive will start again when speed

command is above P240

• P242 > 0.0: Drive will restart when the PID

feedback differs from the setpoint by more
than the value of P242

or when the PID loop

requires a speed above P240.

P241

Sleep Delay

30.0

0.0 {s} 300.0

P242

Sleep Bandwidth

0.0

0.0 B

max

Where: B

max

= |(P205 - P204)|

P243

Feedback Sleep
Entry Threshold

0.0

P204 P205

Active only when P244 = 1 or 2

P244

Sleep Entry Mode

0

0 Enter SLEEP if Drive Speed <P240

For time longer than P241

1 Enter SLEEP if Feedback >P243

For time longer than P241 or same as Sel 0

2 Enter SLEEP if Feedback <P243

For time longer than P241 or same as Sel 0

P245

Sleep Entry Stop
Type

0

0 Coast to Stop
1 Ramp to Stop
2 Stop with P111 settings

P246

Feedback Recovery
from Sleep Threshold

0.0

P204 P205

Active only when P247 = 1 or 2

P247

Sleep Recovery
Mode

0

0 Recovery if Speed Setpoint > P240

or if PID feedback differs from setpoint
by more than P242

1 Recovery only if Feedback < P246
2 Recovery only if Feedback > P246

(2)

Parameter applicable to SMV models 15HP (11kW) and higher.