Commissioning, 6 network parameters – Lenze ESV SMV frequency inverter User Manual

Page 45

Advertising
background image

Lenze SMVector 13465100 EDBSV01 EN v18

43

Commissioning

4.5.6

Network Parameters

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

p400

Network Protocol

0 Not Active

This parameter setting is based upon the network
or I/O module that is installed.

1 Remote Keypad
2 Modbus RTU
3 CANopen
4 DeviceNet
5 Ethernet
6 Profibus
7 Lecom-B
8 I/O Module

p401

Module Type Installed

0

0 No Module Installed

Module type format: 0xAABC; Drive Display:
AA.B.C
AA = Module Type
B = Major revision
C = minor revision

1 Basic I/O (0x0100, 1.0.0)
2 RS485/Rem. Keypad (0x0200, 2.0.0)
3 CANopen (0x0300, 3.0.0)
11 PROFIBUS (0x1100, 11.0.0)
12 Ethernet (0x1200, 12.0.0)

P402

Module Status

0

0 Not Initialized
1 Initialization: Module to EPM
2 Initialization: EPM to Module
3 Online
4 Failed Initialization Error
5 Time-out Error
6 Initialization Failed

Module type mismatch P401

7 Initialization Error

Protocol selection mismatch P400

P403

Module Reset

0

0 No Action

Returns module parameters 401…499 to the
default values shown in the manual

1 Reset parameters to default values

P404

Module Timeout Action

3

0 No Fault

Action to be taken in the event of a Module/
Drive Time-out.
Time is fixed at 200ms
STOP is by the method selected in P111.

1 STOP (see P111)
2 Quick Stop
3 Fault (F_ntF)

P405

Current Network Fault

0 No Fault
1 F.nF1

NetIdle Mode

2 F.nF2

Loss of Ethernet I/O connection

3 F.nF3

Network Fault

4 F.nF4

Explicit Message Timeout

5 F.nF5

Overall Network Timeout

6 F.nF6

Overall Explicit Timeout

7 F.nF7

Overall I/O Message Timeout

P406

Proprietary

Manufacturer specific

p407 P499

Module Specific Parameters

Refer to the Communications Reference Guide
specific to the network or I/O module installed.