Commissioning – Lenze ESV SMV frequency inverter User Manual

Page 31

Advertising
background image

Lenze SMVector 13465100 EDBSV01 EN v18

29

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P110

Start Method

0

0 Normal
1 Start on Power-up

Drive will automatically start when power is
applied.

2 Start with DC Brake

When start command is applied, drive will apply
DC braking according to P174, P175 prior to
starting the motor

3 Auto Restart

Drive will automatically restart after faults, or when
power is applied.

4 Auto Restart with DC Brake

Combines settings 2 and 3

5 Flying Start/Restart - Type 1

• Drive will automatically restart after faults, or

when power is applied.

• After 3 failed attempts, drive will Auto Restart

with DC brake.

• P110 = 5, 7: Performs speed search, starting

at Max Frequency (P103)

• P110 = 6, 8: Performs speed search, starting

at the last output frequency prior to faulting
or power loss

• If P111 = 0, a flying START is performed when

a start command is applied.

• P110 = 7,8: Utilizes P280/281 to set Max

Current Level and Decel Time for restart

6 Flying Start/Restart - Type 1

7 Flying Start /Restart - Type 2

for 2-pole motors requiring a flying
restart

8 Flying Start/Restart - Type 2

for 2-pole motors requiring a flying
restart

NOTE
• P110 = 0, 2: Start command must be applied at least 2 seconds after power-up; F.UF

fault will occur if start command is applied too soon.

• P110 = 1, 3…6: For automatic start/restart, the start source must be the terminal strip

and the start command must be present.

• P110 = 2, 4…6: If P175=999.9, dc braking will be applied for 15s.
• P110 = 3…6: Drive will attempt 5 restarts; if all restart attempts fail, drive displays LC

(fault lockout) and requires manual reset.

• P110 = 5, 6: If drive cannot catch the spinning motor, drive will trip into F.rF fault.

• P110 = 5, 6: If drive trips into F.OF fault, try P110 = 7 or 8.

WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to personnel! Automatic starting/restarting should
only be used on equipment that is inaccessible to personnel.

P111

Stop Method

0

0 Coast

Drive’s output will shut off immediately upon a stop
command, allowing the motor to coast to a stop

1 Coast with DC Brake

The drive’s output will shut off and then the DC
Brake will activate (refer to P174, P175)

2 Ramp

The drive will ramp the motor to a stop according
to P105 or P126.

3 Ramp with DC Brake

The drive will ramp the motor to 0 Hz and then
the DC Brake will activate (refer to P174, P175)

P112

Rotation

0

0 Forward Only

If PID mode is enabled, reverse direction is disabled
(except for Jog).

1 Forward and Reverse