Commissioning, 3 advanced setup parameters – Lenze ESV SMV frequency inverter User Manual

Page 37

Advertising
background image

Lenze SMVector 13465100 EDBSV01 EN v18

35

Commissioning

4.5.3

Advanced Setup Parameters

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

p156

Analog Inputs
Configuration

0

0 TB5: (0-10 VDC); TB25: (4-20mA)
1 TB5: (0 - 5 VDC); TB25: (4-20mA)
2 TB5: (2 - 10 VDC); TB25: (4-20mA)
4 TB5: (0-10 VDC); TB25: (0-20mA)
5 TB5: (0 - 5 VDC); TB25: (0-20mA)
6 TB5: (2 - 10 VDC); TB25: (0-20mA)

p157

TB5 (0-10V) Analog
Input Monitoring
Action

0

0 No Action

Selects the reaction to a loss of the 0-10V signal
at TB5

500ms is the minimum time above/below
Monitoring Level (P158) before triggering the
drive to trip or run at a preset speed.

For P157 = 3 or 6, the accel/decel time is set
in P786.
NOTE: P157 has priority over P163 and TB-13

presets/auto references (P121-P124)

1 If TB5 < P158 - Trip Fault F.FAU
2 If TB5 < P158 - Run Preset #8
3 If TB5 < P158 - Run Preset Seg. #16
4 If TB5 > P158 - Trip Fault F.FAU
5 If TB5 > P158 - Run Preset #8
6 If TB5 > P158 - Run Preset Seg. #16

p158

TB5 (0-10V) Analog
Input Monitoring
Level (ML)

0.0

-10.0 {VDC} 10.0

Negative input voltage is not currently supported.

p159

0-10V Analog Input
Deadband

0.0

0

{VDC} 10.0

Not active if [-10 to +10 VDC] option is selected.

P160

Speed at Minimum
Signal

0.0

-999.0 {Hz} 1000

f

P161

P160

ref

10V

(20mA)

0V

(4mA)

V0111

P161

Speed at Maximum
Signal

60.0

-999.0 {Hz} 1000

NOTE
• P160 sets the output frequency at 0% analog input
• P161 sets the output frequency at 100% analog input
• P160 or P161 < 0.0 Hz: For scaling purposes only; does not indicate opposite direction!
• P160 > P161: Drive will react inversely to analog input signal

p162

Analog Input Filter

0.01

0.00 {s} 10.00

• Adjusts the filter on the analog inputs (TB-5

and TB-25) to reduce the effect of signal noise

• The P162 delay time will affect the response

time of diagnostic parameters (P520-P523).

P163

TB-25 (4-20mA)
Analog Input
Monitoring Action

0

0 No Action

• Selects the reaction to a loss of the 4-20 mA

signal at TB-25.

• Signal is considered lost if it falls below the

value set in P164

• Digital outputs can also indicate a loss of 4-20

mA signal; see P140, P142

• For P163 = 3 or 6, the accel/decel time is

set in P781.

NOTE: P163 has priority over TB-13 presets/auto

references (P121-P124)

1 If TB25 < P164 - Trip Fault F.FoL
2 If TB25 < P164 - Run Preset #7
3 If TB25 < P164 - Run Preset Seg. #15
4 If TB25 > P164 - Trip Fault F.FoL
5 If TB25 > P164 - Run Preset #7
6 If TB25 > P164 - Run Preset Seg. #15