Commissioning – Lenze ESV SMV frequency inverter User Manual

Page 30

Advertising
background image

28

Lenze SMVector 13465100 EDBSV01 EN v18

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P102

Minimum Frequency

0.0

0.0

{Hz} P103

P102, P103 are active for all speed

references

When using an analog speed

reference, also see P160, P161

p103

Maximum Frequency

60.0

7.5

{Hz} 500

NOTE
• P103 cannot be set below Minimum Frequency (P102)
• To set P103 above 120 Hz:

- Scroll up to 120 Hz; display shows HiFr (flashing).

- Release s button and wait one second.
- Press s button again to continue increasing P103.

WARNING!
Consult motor/machine manufacturer before operating above rated frequency. Overspeeding the motor/machine may cause
damage to equipment and injury to personnel!

P104

Acceleration Time 1

20.0

0.0 {s} 3600

• P104 = time of frequency change from 0 Hz to

P167 (base frequency)

• P105 = time of frequency change from P167

to 0 Hz

• For S-ramp accel/decel, adjust P106

P105

Deceleration Time 1

20.0

0.0 {s} 3600

EXAMPLE: IF P103 = 120 Hz, P104 = 20.0 s and P167 (base frequency) = 60 Hz; then the rate of frequency change from 0
Hz to 120 Hz = 40.0 s

P106

S-Ramp Integration
Time

0.0

0.0 {s} 50.0

• P106 = 0.0: Linear accel/decel ramp
• P106 > 0.0: Adjusts S-ramp curve for smoother

ramp

p107

(1)

Line Voltage Selection

1*

0 Low (120, 200, 400, 480VAC)

* The default setting is 1 for all drives except

when using “Reset to 50Hz default settings”
(Parameter P199, selection 4) with 480V
models. In this case, the default setting is 0.

1 High (120, 240, 480, 600VAC)

p108

Motor Overload

100

30

{%} 100

P108 = motor current rating x 100
SMV output rating
Example: if motor = 3amps and SMV = 4amps,
then P108 = 75%

NOTE
Do not set above rated motor current as listed on the motor dataplate. The motor thermal
overload function of the SMV is UL approved as a motor protection device. Cycling power after
an overload fault could result in significantly reducing the motor life.

P109

Motor Overload Type

0

0 Speed Compensation

Ir

100%

60%

30 f

1

0

V0108

1 No Speed Compensation
Example: Motor is cooled by forced
ventilation as apposed to shaft mounted,
self cooling fans.

(1)

Any changes to this parameter will not take effect until the drive is stopped.