32

Lenze SMVector 13465100 EDBSV01 EN v18

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

NOTE
• When input is activated, settings 1...7 override P101
• When TB-13A...TB-13D are configured for Auto References other than MOP, TB-13D overrides TB-13C, TB-13C overrides

TB-13B and TB-13B overrides TB-13A. Any other Auto Reference will have priority over MOP.

• Settings 10...14 are only valid in Terminal Strip mode (P100 = 1, 4, 5, 6)
• If Start/Run/Jog Forward and Start/Run/Jog Reverse are both activated, drive will STOP
• If Jog input is activated while drive is running, the drive will enter Jog mode; when Jog input is deactivated, drive will STOP
• An F.AL fault will occur if the Assertion Level switch (ALsw) position does not match the P120 setting and any of the digital

inputs (P121...P124) are set to a value other than 0.

• An F.IL fault will occur under the following conditions:

- TB-13A...TB-13D settings are duplicated (each setting, except 0, 3 and 23, can only be used once)
- One input is set to “MOP Up” and another is not set to “MOP Down”, or vice-versa.
- One input is set to 10 and another input is set to 11…14.
- One input is set to 11 or 12 and another input is set for 13 or 14.

• Typical control circuits are shown below:

- If any input is set to 10, 12 or 14, P112 must be set to 1 for Reverse action to function.

Run / Stop

with Direction

P121 = 10

Start Forward /

Start Reverse

P121 = 11, P122 = 12

Run Forward /

Run Reverse

P121 = 13, P122 = 14

1

4

13A

FWD

REV

STOP

RUN

1

4

13A 13B

RUN

REV

RUN

FWD

FWD

REV

STOP

1

4 13A 13B

P125

Acceleration Time 2

20.0

0.0 {s} 3600

• Selected using TB-13A...TB-13D (P121...

P124 = 17)

• For S-ramp accel/decel, adjust P106

P126

Deceleration Time 2

20.0

0.0 {s} 3600

p127

Deceleration Time
for Auxiliary Ramp
to Stop

20.0

0.0 {s} 3600

• Selected using TB-13A...TB-13D (P121...

P124 = 19).

• For S-ramp accel/decel, adjust P106
• Once executed, this ramp time has priority over

P105 and P126.

p129

Automatic Accel/
Decel rate switch
threshold

0.0

0.0

{Hz} 1000

If Actual Frequency < P129 Use Accel/decel time
#2 (P125/P126)
If Actual Frequency > P129 Use Accel/decel time
#1 (P104/P105)

p131

Preset Speed #1

0.0

0.0

{Hz} 500

PRESET

SPEED

13A

13B

13C

13D

1

X

--

--

--

2

--

X

--

--

3

--

--

X

--

4

X

X

--

--

4 (alternate)

--

--

--

X

5

X

--

X

--

6

--

X

X

--

7

X

X

X

--

8 (alternate)

--

X

--

X

8 (alternate

--

--

X

X

• Speed setting is used by P158
• 13D available on 15HP (11kW) & higher drives.

p132

Preset Speed #2

0.0

0.0

{Hz} 500

p133

Preset Speed #3

0.0

0.0

{Hz} 500

p134

Preset Speed #4

0.0

0.0

{Hz} 500

p135

Preset Speed #5

0.0

0.0

{Hz} 500

p136

Preset Speed #6

0.0

0.0

{Hz} 500

p137

Preset Speed #7

0.0

0.0

{Hz} 500

p138

Preset Speed #8

0.0

0.0

{Hz} 500