Safety information – Lenze ESV SMV frequency inverter User Manual

Page 7

Advertising
background image

Lenze SMVector 13465100 EDBSV01 EN v18

5

Safety Information

Harmonics Notification in accordance with EN 61000-3-2, EN 61000-3-12:

Operation in public supply networks (Limitation of harmonic currents i.a.w. EN 61000-3-2,
Electromagnetic Compatibility (EMC) Limits). Limits for harmonic current emissions (equipment input
current up to 16A/phase).

Directive

Total Power

connected to Mains

(public supply)

Additional Measures Required for Compliance

(2)

EN 61000-3-2

< 0.5kW

with mains choke

0.5 ... 1kW

with active filter

> 1kW

complies without additional measures

EN 61000-3-12

16 ... 75amp

Additional measures are required for compliance with the standard

(1) For compliance with EMC regulations, the permissable cable lengths may change.
(2) The additional measures described only ensure that the controller meets the requirements of the EN 61000-3-2.

The machine/system manufacturer is responsible for the machine’s compliance with the regulations.

Safety Information in accordance with EN 61800-5-1:

DANGER! - Risk of Electric Shock
Capacitors retain charge for approximately 180 seconds after power is removed. Disconnect
incoming power and wait at least 3 minutes before touching the drive.

DANGER! - Risque de choc électrique
Les condensateurs restent sous charge pendant environ 180 secondes après une coupure
de courant. Couper l’alimentation et patienter pendant au moins 3 minutes avant de toucher
l’entraînement.

WARNING!

• This product can cause a d.c. current in the PE conductor. Where a residual current-

operated (RCD) or monitoring (RCM) device is used for protection in case of direct or
indirect contact, only an RCD or RCM Type B is allowed on the supply side of this product.

• Leakage Current may exceed 3.5mA AC. The minimum size of the PE conductor shall

comply with local safety regulations for high leakage current equipment.

• In a domestic environment, this product may cause radio interference in which case

supplementary mitigation measures may be required.