Lenze SMVector 13465100 EDBSV01 EN v18

Commissioning

4.5.8

Onboard Communications Parameters 15-60HP (11-45kW)

The P6xx Onboard Communication parameters are applicable to the 15HP (11kW) and higher models only.

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

p600

Network Enable

0

0 Disabled

This parameter enables the onboard network
communications.

1 Remote Keypad
2 Modbus
7 Lecom
NOTE: Onboard Communications will be
disabled if:

- P600 = 0, or
- P600 = 1 and P400 = 1, or
- P600 = 2 and P400 = 2, 3, 4, 5, 6 or 7
- P600 = 7 and P400 = 2, 3, 4, 5, 6 or 7

If the onboard communications are disabled,
the user will not have access to any of the other
P6xx parameters.

P610

Network Address

1

1 - 247

Modbus

1

1 - 99

Lecom

P611

Network Baud Rate

2

0 2400 bps

2 9600 bps

Modbus

1 4800 bps

3 19200 bps

0

0 9600 bps

Lecom

1 4800 bps
2 2400 bps
3 1200 bps
4 19200 bps

P612

Network Data Format

0

0 8, N, 2

Modbus Only

1 8, N, 1
2 8, E, 1
3 8, O, 1

P620

Network Control
Level

0

0 Monitor Only

Lecom Only

1 Parameter Programming
2 Programming and Setpoint Control
3 Full Control

P624

Network Powerup
Start Status

0

0 Quick Stop

Lecom Only

1 Controller Inhibit

p625

Network Timeout

10.0

0.0 - 300.0 seconds

Modbus

50

0 - 65000 milliseconds

Lecom

P626

Network Timeout
Action

4

0 No action

Modbus

1 Stop (P111)
2 Quick Stop
3 Controller Inhibit
4 Trip Fault, F.nF1

0

0 No action

Lecom

1 Controller Inhibit
2 Quick Stop
3 Trip Fault, F.nF1

P627

Network Messages
Received

Read-Only: 0 - 9999

Valid network messages received

NOTE: When the number of messages exceeds 9999, the counter resets and resumes
counting from 0.