Commissioning, 5 parameter menu, 1 basic setup parameters – Lenze ESV SMV frequency inverter User Manual

Page 29

Advertising
background image

Lenze SMVector 13465100 EDBSV01 EN v18

27

Commissioning

4.5

Parameter Menu

4.5.1

Basic Setup Parameters

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P100

Start Control Source

0

0 Local Keypad

Use RUN button on front of drive to start

1 Terminal Strip

Use start/stop circuit wired into the terminal strip.
Refer to section 3.2.3

2 Remote Keypad Only

Use RUN button on optional Remote Keypad to start

3 Network Only

• Start command must come from network

(Modbus, CANopen, etc)

• SMV models <15HP (11kW) require optional

communication module (refer to the network
module documentation).

• Must also set one of the TB-13 inputs to 9

(Network Enable); see P121...P124

4 Terminal Strip or Local Keypad

Allows start control to be switched between
terminal strip and local keypad using one of the
TB-13 inputs. See note below.

5 Terminal Strip or Remote Keypad

Allows start control to be switched between
terminal strip and optional remote keypad using
one of the TB-13 inputs. See Note below

6 CTRL button select

Allows start control to be switched between
terminal strip and local keypad using the CTRL
button.
NOTE: P100 Selection 6 is applicable to SMV 15HP
(11kW) and higher models only.

WARNING!
P100 = 0 disables TB-1 as a STOP input! STOP circuitry may be disabled if parameters are
reset back to defaults (see P199)
NOTE
• P100 = 4, 5: To switch between control sources, one of the TB-13 inputs (P121...P124)

must be set to 08 (Control Select);
TB-13x OPEN (or not configured): Terminal strip control
TB-13x CLOSED: Local (P100 = 4) or Remote (P100 = 5) keypad

• P100 = 0, 1, 4, 6: Network can take control if P121...P124 = 9 and the corresponding

TB-13x input is CLOSED.

• The STOP button on the front of the drive is always active except in JOG mode.
• TB-1 is an active STOP input if P100 is set to a value other than 0.

• An

F.AL

fault will occur if the Assertion Level switch (ALsw) position does not match

the P120 setting and P100 is set to a value other than 0.

P101

Standard Reference
Source

0

0 Keypad (Local or Remote)

Selects the default speed or torque reference
when no Auto Reference is selected using the
TB-13 inputs.

1 0-10 VDC
2 4-20 mA
3 Preset #1 (P131)
4 Preset #2 (P132)
5 Preset #3 (P133)
6 Network
7 Preset Sequence Segment #1 (P710) Selections 7, 8 & 9 are not valid for PID setpoint

or torque reference.

8 Preset Sequence Segment #2 (P715)
9 Preset Sequence Segment #3 (P720)