Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

p175

DC Brake Time

0.0

0.0 {s} 999.9
NOTE: CONFIRM MOTOR SUITABILITY FOR USE WITH DC BRAKING
DC Brake voltage (P174) is applied for the time specified by P175 with the following exceptions:
• If P111=1, 3 and P175=999.9 the brake voltage will be applied continuously until a run

or fault condition occurs.

• If P110=2, 4…6 and P175=999.9, brake voltage will be applied for 15s
• If P121…P124=18 and the corresponding TB-13 input is CLOSED, brake voltage will be

applied until the TB-13 input is OPENED or a fault condition occurs.

p176

Keypad Setpoint
Single Press
Increment

0.1

0.1 100.0

Used for run screen setpoint editing only.
If P176 >0.1 then scrolling of keypad setpoint
is enabled.

p177

(2)

Speed Units

0

0 Hz

Select the UNITS LED that will be illuminated when
the drive is running in speed control mode. For this
parameter to be used, P178 must be set to a value
other than 0. IF P178 is set to 0, the Hz LED will
be illuminated regardless of the value set in P177.

1 RPM
2 %
3 /UNITS
4 NONE

p178

Display Frequency
Multiplier

0.00

0.00 650.00

• Allows frequency display to be scaled
• P178 = 0.00: Scaling disabled
• P178 > 0.00: Display = Actual Frequency

X P178

EXAMPLE
If

P178 = 29.17 and actual frequency = 60 Hz, then Drive displays 1750 (rpm)

p179

Run Screen Display

0

0 {Parameter Number}

599

• 0 = Normal Run Screen, this display depends

on mode of operation. Refer to section 4.2.

• Other selections choose a diagnostic parameter

to display (P501…P599).

• Parameters P560 - P564 are selectable if

the sequencer is enabled (P700 is not 0).
P560-P564 are not visible until P700 is
enabled.

p180

Oscillation Damping
Control

0

0 80

0 = Damping disabled
Compensation for resonances within drive

p181

Skip frequency 1

0.0

0.0

{Hz}

500

• Drive will not run in the defined skip range;

used to skip over frequencies that cause
mechanical vibration

• P181 and P182 define the start of the skip

ranges

• P184 > 0 defines the bandwidth of both ranges.

p182

Skip frequency 2

0.0

0.0

{Hz}

500

p184

Skip frequency
bandwidth

0.0

0.0

{Hz}

10.0

NOTE
Bandwidth (Hz) = f

s

(Hz) + P184 (Hz) f

s

= P181 or P182

EXAMPLE: P181 = 18 Hz and P184 = 4 Hz; skip range is from 18 to 22 Hz

p185

Voltage Midpoint
V/Hz characteristic

0

0.0

{V}

P165

Valid only when P300 = 0 or 2.
Use with P187 to define midpoint on V/Hz curve.

p187

(2)

Frequency Midpoint
V/Hz characteristic

0.0

0.0

{Hz}

P167

Valid only when P300 = 0 or 2.
Use with P185 to define midpoint on V/Hz curve.

p189

(3)

Integrated Dynamic
Brake

0 Disabled
1 Enabled

(2)

Parameter applicable to SMV models 15HP (11kW) and higher.

(3)

Parameter applicable to SMV models 40HP (30kW) and higher.