Lenze SMVector 13465100 EDBSV01 EN v18

31

Commissioning

4.5.2

I/O Setup Parameters

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

p120

Assertion Level

2

1 Low

P120 and the Assertion Level switch must both
match the desired assertion level unless P100,
P121…P124 are all set to 0. Otherwise an F.AL
fault will occur.

2 High

P121

p122

p123

p124

TB-13A Digital Input

TB-13B Digital Input

(Priority > TB13A)
Same as TB13A except:

3 = Preset #2
23 = Seq Seg, #2

TB-13C Digital Input

(Priority > TB13B, A)
Same as TB13A except:

3 = Preset #3
23 = Seq Seg, #4

TB-13D* Digital Input

(Priority > TB13C, B, A)
Same as TB13A except:

3 = Preset #4
23 = Seq Seg, #8

0

0 None

Disables input

1 AUTO Reference: 0-10 VDC

For frequency mode, see P160...P161,
For PID mode, see P204…P205,
For vector torque mode, see P330

2 AUTO Reference: 4-20 mA

3 AUTO Reference: Preset #1

* 13D: 3 = Reserved

For frequency mode see P131...P137,
For PID mode, see P231…P233,
For torque mode see, P331…P333

4 AUTO Reference: MOP Up

• Normally open: Close input to increase or

decrease speed, PID or torque setpoint.

• MOP Up is not active while in STOP

5 AUTO Reference: MOP Down

6 AUTO Reference: Keypad
7 AUTO Reference: Network
8 Control Select

Use when P100 = 4, 5 to switch between terminal
strip control and local or remote keypad control.

9 Network Enable

Required to start the drive through the network.

10 Reverse Rotation

Open = Forward Closed = Reverse

11 Start Forward

Refer to Note for typical circuit

12 Start Reverse
13 Run Forward

Refer to Note for typical circuit

14 Run Reverse
15 Jog Forward

Jog Forward speed = P134

16 Jog Reverse

Jog Reverse speed = P135

Active even if P112 = 0

17 Accel/Decel #2

Refer to P125, P126

18 DC Brake

Refer to P174; close input to override P175

19 Auxiliary Ramp to Stop

Normally closed: Opening input will ramp drive
to STOP according to P127, even if P111 is set
to Coast (0 or 1).

20 Clear Fault

Close to reset fault

21 External Fault F.EF

Normally closed circuit; open to trip

22 Inverse External Fault F.EF

Normally open circuit; close to trip

23 AUTO Ref: Sequence Segment #1

Works in Speed Mode only

24 Start Sequence
25 Step Sequence

Transition from non-asserted to asserted state

26 Suspend Sequence

WARNING
Jog overrides all STOP commands! To stop the drive while in Jog mode, the Jog input must be deactivated or a
fault condition induced.
WARNING
If the input defined to “Start Sequence” is opened during a sequence, the drive will exit sequencer mode and will run
at the specified standard or alternate speed source (dependent on drive configuration).

NOTE: P124 is
applicable to SMV
15HP (11kW) and
higher models only