C13881 | overall ethernet timeout time, C13885 | clear i/o data, C13899 | hostname – Lenze E84DGFCG User Manual

Page 104: C13900 | firmware product type, C13901 | firmware compilation date, C13885, C13881, There is no longer any access, E timeout time, Parameter reference

Advertising
background image

Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013

104

Parameter reference

Parameters of the Communication Unit

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13881

C13885

C13899

C13900

C13901

Parameter | Name:

C13881 | Overall Ethernet Timeout Time

Data type: UNSIGNED_16

Index: 10694 = 0x29C6

Setting of the overall monitoring time (see

Fault with regard to EtherNet/IP communication ( 77)

)

A change in the monitoring response becomes immediately effective.
Setting range

(min. value | unit | max. value)

Lenze setting

500

ms

65535 10000 ms

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13885 | Clear I/O Data

Data type: UNSIGNED_8

Index: 10690 = 0x29C2

Setting which I/O data are to be processed by the adapter to maintain internal communication if ...

• the network status of the controlling I/O connection is "Not connected" (see

C13862

) or

• an idle event has occurred.

Changes in the setting becomes effective immediately.

(See

Fault with regard to EtherNet/IP communication ( 77)

.)

Selection list

(Lenze setting printed in bold)

0 Use of last Scanner Output Data
1 Clear Scanner Output Data

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13899 | Hostname

Data type: VISIBLE_STRING

Index: 10676 = 0x29B4

Each subcode contains a string with a length of 32 bytes indicating the designation of the EtherNet/IP node.

(Instance attribute 6 (Host Name) in the

TCP/IP Interface Object (245 / 0xF5) ( 126)

)

Subcodes

Lenze setting

Info

C13899/1

Host name

C13899/2

Host name

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13900 | Firmware Product Type

Data type: VISIBLE_STRING

Index: 10675 = 0x29B3

The code contains a string with a length of 8 bytes. The identification code "E84DGFCG" is displayed.

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13901 | Firmware Compilation Date

Data type: VISIBLE_STRING

Index: 10674 = 0x29B2

The code contains a string with a length of 20 bytes. The software creation date ("MMM DD YYYY") and time

("hh:mm:ss") are displayed (e.g. "Mar 21 2005 12:31:21").

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT