Commissioning

Configuring the host system (scanner)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.2.2

Example: IP configuration of the Allen-Bradley 1769-L32E CompactLogix controller

In this example, the Allen-Bradley 1769-L32E CompactLogix controller with integrated EtherNet/IP

interface is used to communicate with Inverter Drives 8400 motec.
The »RSLogix 5000« programming software from Rockwell is used for the configuration.
To establish communication via an EtherNet/IP network, add the controller and its scanner to the I/

O configuration.

How to set the IP configuration of the 1769-L32E CompactLogix controller using the

»RSLogix 5000« programming software:

1. Click on the I/O Configuration folder in the configuration tree.
2. Right click on "1769-L32E Ethernet Port LocalENB" and select "Properties" from the context

menu.

3. Go to the General tab of the "Module Properties: ..." dialog window and enter the IP address

of the scanner.

4. Then click OK.