I/O data transfer (implicit messages)

I/O configuration with »RSLogix 5000« version 19 or lower

57

Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.6

I/O configuration with »RSLogix 5000« version 19 or lower

The following example describes the I/O configuration of the Allen-Bradley 1769-L32E

CompactLogix controller using the Rockwell »RSLogix 5000« programming software up to version

19.
Up to and including software version 19, the I/O configuration is carried out without EDS files.

How to carry out the I/O configuration, taking the CompactLogix controller 1769-L32E

with »RSLogix 5000« as an example:

1. Click the I/O Configuration folder in the configuration tree.

For the 1769-L32E CompactLogix controller, the I/O configuration already includes a local Ethernet

port.
If a SoftLogic or ControlLogix controller is used, an Ethernet port scanner needs to be added to the

configuration.