5 initial switch-on, Initial switch-on, Commissioning – Lenze E84DGFCG User Manual

Page 39

Advertising
background image

Commissioning

Initial switch-on

39

Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.5

Initial switch-on

Establishing communication

• To establish a communication, the Inverter Drive has to be supplied with mains voltage.
• For EtherNet/IP communication, the Communication Unit has to be supplied with voltage.

If this is not the case, the error message "CE04: MCI communication error" (error no.

01.0127.00002) is output. The error has to be reset in the Inverter Drive in order that the

EtherNet/IP communication can be established.

• The external voltage supply serves to maintain EtherNet/IP communication if the main supply

fails.

External voltage supply

( 24)

• During mains connection, all parameters (codes) are read.
• For addressing the drive, a valid IP configuration is required if communication between the PC/

»Engineer« and the drive is to be effected via EtherNet/IP.

Setting the IP configuration of the Inverter Drive 8400 motec

( 30)

Advertising