Commissioning

Setting the IP configuration of the Inverter Drive 8400 motec

33

Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.3.2

Setting via codes in the »Engineer«

You can also set the IP parameters manually in the »Engineer« under the Settings tab. The values

will be transferred to the corresponding codes.

How to activate changed settings in the »Engineer«:

1. Execute device command C00002 = "11: Save all parameter sets".

The current IP configuration is stored in the memory module of the drive.

2. Carry out a "Type 0 reset" for the

Identity Object (1 / 0x01)

( 110)

of the node, or switch the

voltage supply of the Communication Unit off and on again.

Settings

Description

IP Config Control

Selection (

C13005

) of how the IP configuration is to be made:

0: The IP configuration currently saved in the Communication Unit is

used.

1: The IP configuration is assigned by a BOOTP server using the BOOTP.

2: The IP configuration is assigned by a DHCP server using the DHCP.

IP Address

Setting of the IP address (

C13000

)

Subnet mask

Setting of the subnet mask (

C13001

)

Gateway Address

Setting of the gateway address (

C13002

)

Multicast IP Start Address

Setting of the Multicast IP start address (

C13006

)

Setting the multicast configuration ( 36)

Multicast Config TTL Value

Setting of the multicast TTL value (

C13019

)