EtherNet/IP: Restart by watchdog reset [0x01bc6010]

EtherNet/IP: Internal Error [0x01bc6011]

EtherNet/IP: Internal error [0x01bc6100]

EtherNet/IP: Internal error [0x01bc6101]

EtherNet/IP: Invalid parameter set [0x01bc641f]

EtherNet/IP: Lenze setting Loaded [0x01bc6420]

Response (Lenze setting printed in bold)

Setting: C01501/2 ( Adjustable response)

No reaction  System fault  Fault  Trouble  TroubleQuickStop  WarningLocked  Warning  Information

Cause

Remedy

Device is defective.

Send the device and a description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting: C01501/2 ( Adjustable response)

No reaction  System fault  Fault  Trouble  Quick stop by trouble  WarningLocked  Warning  Information

Cause

Remedy

Device is defective.

Send the device and a description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting: C01501/2 ( Adjustable response)

No reaction  System fault  Fault  Trouble  TroubleQuickStop  WarningLocked  Warning  Information

Cause

Remedy

Device is defective.

Send the device and a description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting: C01501/2 ( Adjustable response)

No reaction  System fault  Fault  Trouble  TroubleQuickStop  WarningLocked  Warning  Information

Cause

Remedy

Device is defective.

Send the device and a description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting: C01501/2 ( Adjustable response)

No reaction  System fault  Fault  Trouble  TroubleQuickStop  WarningLocked  Warning  Information

Cause

Remedy

No active parameter set could be loaded.

• Download application again (including module).

• Send the device and a description of the fault to

Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Access to parameter set was not possible.

• Download application again (including module).

• Send the device and a description of the fault to

Lenze.