I/O data transfer (implicit messages)
I/O configuration with »RSLogix 5000« version 20 or higher
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Settings for an "AC Drive Profile" application:
•
Select "AC Drive" connection.
In the example, the AC Drive Profile "Exclusive Owner - AC Drive Ext. Speed & Torque" is
used.
•
Set Data type = INT.
The INT data type is exchanged via the ports MCI_IN and MCI_OUT of the Inverter Drives
8400. In case of the SINT data type, an additional PLC logic is required for conversion.
•
Set Tag Suffix = 1.
A tag suffix formulates a module-describing tag name.
9. Complete the settings with OK.