Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013

60

I/O data transfer (implicit messages)

I/O configuration with »RSLogix 5000« version 19 or lower

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Settings for an "AC Drive Profile" application:

The assembly object instances

"Input = 73" and

"Output = 23" shown here

exemplify the use of the AC Drive Profile "Extended Speed and Torque".

6. Complete the settings with OK.

Settings

Description

Name

Device name or type of the drive, usually with reference to the process (in the

example "My_8400_motec")

Comm Format

Data format for the assembly object instances ("connection parameters" area)

IP Address

IP address of the drive

• The IP address must be in the same subnetwork like the controller. (Depending on

the subnet mask; in general, the first 3 octets of the IP address must be identical.)

• DNS is not supported; the host name merely describes the device.

Input

Assembly object instance for input objects

• Max. 10 input data words (20 bytes, 16 bits/word)

• The number of input data must correspond to the length of the mapped ports in

the transmit PDO (PDO_TX0), otherwise the adapter will reject the connection

with the error message "Invalid Target to Originator Size" (0x0128).

• In the 111 (0x6F, Custom Input) assembly object instance, the I/O data is entered

in the last two words (see

Configuring I/O data ( 45)

)

I/O data mapping ( 47)

Output

Assembly object instance for output objects

• Max. 8 output data words (16 bytes, 16 bits/word)

• The number of output data must correspond to the length of the mapped ports

in the receive PDO (PDO_RX0), otherwise the adapter will reject the connection

with the error message "Invalid Originator to Target Size" (0x0127).

I/O data mapping ( 47)

Configuration

Select the Assembly instance "130" and the Size "0" for the configuration. These

values are required!